Free to use No registration 100% private Instant results Metric & Imperial

Cable Sizing Calculator

Ampacity tells you the minimum safe wire size; voltage drop tells you the actually useful size for long runs. This calculator computes the real voltage drop for your circuit — accounting for the round-trip conductor path — checks the 60°C ampacity limit, and suggests the gauge that keeps the drop under 3%, the NEC-recommended target for branch circuits.

Circuit Parameters

The Voltage Drop Formula

Drop is proportional to resistance and distance, and doubled for the return path:

Vdrop = 2 × one-way length × Rper 1000 ft × I ÷ 1000

At 120 V, 20 A, over 50 ft of 12 AWG (R = 1.93 Ω/1000 ft): drop = 2 × 50 × 1.93 × 20 ÷ 1000 = 3.9 V (3.2%). That is already above the 3% guidance — most "12 AWG for 20 amps" advice quietly assumes a short run. Stretch the same circuit to 100 ft and the drop doubles to 6.4%, which is why long garage and outbuilding runs always need a size or two larger.

Ampacity and Common Wire Sizes

AWGAmpacity (60°C)Drop / 100 ft @20 ATypical Use

Ampacity values are for copper at 60°C termination. Drop figures assume 100 ft one-way, 120 V, 20 A. Always follow local code and equipment terminal ratings.

How to Use This Calculator (3 Steps)

1
Enter voltage and true load current
Use the load current, not the breaker rating. Continuous loads should be sized at 125% (an 80% rule keeps a 16 A continuous load on a 20 A breaker). Motor circuits should use nameplate FLA.
2
Measure the real run length
The one-way distance from panel to load is what you enter — the calculator doubles it. Include the vertical rise and any bends; underestimating length underestimates drop.
3
Compare selected vs recommended gauge
If your gauge shows over 3%, step up to the recommended size. If the result flags over-ampacity, the wire is a fire hazard regardless of drop — that is always a code violation.

Case Study

🔌
Case Study #1

A 100-Foot Run to a Detached Garage

A homeowner needs a 20 A, 120 V circuit fed 100 ft to a garage workshop with a table saw and lighting.

12 AWG Drop
6.4%
10 AWG Drop
4.0%
8 AWG Drop
2.6%
Recommended
8 AWG

Frequently Asked Questions

How do I size a cable for voltage drop?

Drop = 2 × length × resistance × current ÷ 1000. Pick the gauge under 3% for the run.

What is the 3% voltage drop rule?

NEC guidance: feeders + branch circuits should stay within 3% (5% total). Exceeding it dims lights and overheats motors.

What wire size for 20 amps?

12 AWG copper, standard for 20 A branch circuits. Long runs may need 10 AWG for voltage drop.

Why does drop matter on long runs?

Resistance grows with length — 200 ft has 4× the drop of 50 ft at the same current.

One-way or two-way?

Two-way. Current returns on the neutral, so the formula uses 2 × one-way length.

B
BuildFormulas Electrical Team
Wiring & Load Analytics

The BuildFormulas Electrical Team builds wiring, load, and power calculators for electricians, engineers, and DIYers, grounded in NEC ampacity tables and conductor resistance data.

Reviewed by BuildFormulas Editorial Review Board, Editorial Review
Last updated: August 2026