Electrician Calculator

7 professional electrical tools in one calculator. Ohm's Law, power triangle, voltage drop, wire sizing, load calculations, motor FLA, and conduit fill. All calculations follow NEC 2023 standards.

⚡ Ohm's Law Calculator

Enter any 2 values and the others are calculated. V = I × R, P = V × I.

Calculated Values

P = V × I
1200 W
I = V / R
10 A
R = V / I
12 Ω
V = I × R
120 V
I = P / V
10 A
V = P / I
120 V

Ohm's Law Triangle

The Ohm's Law Triangle is a visual mnemonic: V at top, I and R at bottom. Cover the unknown variable and the remaining two show the formula.

Power variations: P = V × I = I² × R = V² / R. These derived formulas let you calculate power without measuring current or voltage directly.

Practical tip: For troubleshooting, measure resistance of loads (with power off). Then use V and R to predict current draw.

Case Study #1

Kitchen Remodel: Undersized Wire Causes Fire Risk

A homeowner's contractor used #12 wire for a 150ft run to a 240V oven. Voltage drop was 9.3% - a fire hazard.

#12 VD
9.3% (VIOLATION)
#8 VD (correct)
2.9% (safe)
Cost difference
$60 more for #8
Fire risk
HIGH with #12

Wire Size vs Distance at 240V / 20A

WireVD at 75ftVD at 100ftVD at 150ftVD at 200ft

Electrical Fundamentals: Complete Reference Guide

Ohm's Law: The Foundation of Electrical Engineering

Ohm's Law states that current (I) through a conductor is proportional to voltage (V) across it and inversely proportional to resistance (R): V = I × R.

Power variations: P = V × I = I² × R = V² / R. These derived formulas let you calculate power without measuring current or voltage directly.

Practical tip: For troubleshooting, measure resistance of loads (with power off). Then use V and R to predict current draw. Most household loads are between 10-20 ohms at 120V.

Power Triangle: Real, Apparent, and Reactive Power

Real Power (P): Watts (W) - actual work done. Apparent Power (S): Volt-Amps (VA) - total power supplied. Reactive Power (Q): VAR - power in magnetic fields.

Power Factor = P / S. Higher PF means less wasted energy. Industrial facilities install capacitor banks to correct PF above 0.95, reducing demand charges by 5-15%.

Voltage Drop: Why Wire Size Matters Over Distance

Every wire has resistance. When current flows, some voltage is lost as heat. This is voltage drop. Formula: VD = 2 × L × I × R / 1000.

NEC Recommendation: Max 3% for branch circuits, 5% total. Exceeding these limits causes motor burnout, flickering lights, and nuisance breaker trips.

Wire Sizing: NEC Table 310.15(B)(16)

Ampacity: Maximum current a wire can carry continuously. Based on conductor material, insulation type, and ambient temperature.

125% Rule (NEC 210.19): Continuous loads (3+ hours) require wire rated for 125% of load current. A 20A continuous load needs wire rated for 25A minimum.

Breaker Protection (NEC 240.4): Wire ampacity must equal or exceed the breaker rating. Never put a 30A breaker on #14 wire (rated 15A).

Motor Circuits: NEC Chapter 430 Requirements

Wire (430.22): 125% of motor FLA. Breaker (430.52): 250% of FLA (inverse-time). Overload (430.32): 115-125% of FLA. Motor circuits follow unique rules separate from general branch circuits due to high inrush current (5-7x FLA at startup).

Frequently Asked Questions

What size wire do I need for a 20-amp circuit?

For a 20A circuit, use #12 AWG copper wire minimum (rated 20A). For runs longer than 75ft at 120V or 150ft at 240V, upsize to #10 AWG to stay within 3% voltage drop.

How do I calculate voltage drop?

VD = 2 x L x I x R / 1000. L is one-way distance in feet, I is current in amps, R is resistance in ohms per 1000 feet. The 2 accounts for the round-trip (hot + neutral).

Can I use aluminum wire instead of copper?

Yes, for service entrance and feeders. Aluminum is lighter and cheaper but requires larger gauge (#4 AL = #6 CU ampacity). Use anti-oxidant paste at connections. Never use aluminum for branch circuits.

What breaker do I need for a 5 HP motor?

A 5 HP single-phase 230V motor has FLA of ~28A (NEC Table 430.248). Use a 70A breaker (250% rule) and #8 AWG wire (125% of FLA = 35A minimum).

What is the NEC maximum voltage drop?

NEC recommends (not mandates) 3% for branch circuits and 5% total. Exceeding limits voids equipment warranties and can cause motor burnout and flickering lights.

How do I fill a conduit properly?

Use NEC Chapter 9 tables. Max fill: 1 wire = 53%, 2 wires = 31%, 3+ wires = 40%. For example, 4 #12 THHN wires need at least 1/2 inch EMT.

Related Calculators

🧱
Concrete Calculator
Concrete volume estimates
🪵
Lumber Calculator
Lumber pricing and volume
☀️
Solar Calculator
Solar panel sizing
🔌
EV Charger Cost
EV charging costs

References & Sources

  • NFPA 70 - National Electrical Code (NEC) 2023 - The authoritative standard for safe electrical installation. Published by the National Fire Protection Association.
  • NEC Table 310.15(B)(16) - Allowable ampacities of insulated conductors. The primary reference for wire sizing.
  • NEC Chapter 430 - Motors, Motor Circuits, and Controllers. Comprehensive requirements for motor branch circuits.
  • NEC Chapter 9, Table 1 - Percent Area of Conduit or Tubing for Conductors. Standard for conduit fill calculations.
  • NEC Table 430.248 - Full-Load Current, Single-Phase AC Motors. Reference for motor FLA calculations.
  • IEEE Standard 141-1993 - IEEE Recommended Practice for Electric Power Distribution for Industrial Plants (Red Book).
  • U.S. Department of Energy - Improving Power Factor to Reduce Electricity Demand Charges.
B
BuildFormulas Electrical Engineering Team
Licensed Electricians & NEC Compliance Experts

Calculations verified against NEC 2023 (NFPA 70). All wire sizing, ampacity, and voltage drop calculations follow NFPA 70 standards.